Application
Intermittent Pilot Ignition Control
Control Voltage
Line 24V (18-30 VAC), 50/60Hz
Anticipator Setting
0.3A plus valve load @ 24VAC
Pre-purge
15 seconds
Trial for ignition
85 seconds
Lockout
60 minutes
Flame Failure Response Time
2 seconds
WEIGHT/DIMENSIONS
Weight: 0.5, Height: 1.875, Width: 3.125, Length: 4.75
Brands Supported
JCI / Lennox
Item Shipping Weight (lbs.)
0.50
- Intermittent pilot gas ignition control
- For use with intermittent pilot boilers, furnaces and other heating appliances
- Microprocessor-based precision
- Monitors timing, trial for ignition, flame sensing and lockout
- Remote flame sensing
- 100% lockout safety feature
- Works with both Natural and LP gas systems
- Status LED for fault codes to aid in troubleshooting