Application
Intermittent Pilot Retrofit Kit
Ignition System Type
Intermittent Pilot
Pilot Type
Intermittent
Ignition Source
Internal high voltage spark generator
Ignition Between Trail Time
5 minute delay after failed trial for ignition.
Ignition Sequence
Continuous Retry
Ignitor Electrical Rating
24 V AC
Pre-Purge
0 or 30 seconds
Lockout Timing
15 or 90 seconds
Flame Failure Response Time
2 seconds maximum
Flame Sense
Two Rod, Single Rod
Maximum Valve Load
1A Pilot, 2A Main @ 24Vac
Frequency
60 Hz
Compatible With
Intermittent pilot warm air furnaces and heating appliances
Includes
VR8304M3558 gas valve, Ignition module, Pilot burner hardware, Ignition cable, Wiring harness
- Y8610U kits can be used with either natural or LP gas.
- The S8610U ignition control provides a 90 second maximum ignition trial, shuts off, waits five minutes nominal, then re-initiates the pilot ignition sequence.
- The ignition trial, shutoff, and wait cycle repeat until the pilot lights or the call for heat ends.