Application
Smoke Detetor
MODEL NUMBER
D4120
POWER REQUIREMENTS: (without accessories) Standby:
21 mA @ 24VDC / 65 mA RMS @ 24VAC 60Hz / 20 mA RMS @ 120VAC 60Hz
POWER REQUIREMENTS: (without accessories) Alarm:
65 mA @ 24VDC / 135 mA RMS @ 24VAC 60Hz / 35 mA RMS @ 120VAC 60Hz
Alarm Contacts Rating:
(SPST) 2.0A @ 30 VDC (resistive) / (DPDT) 10A @ 30 VDC (resistive); 10A @ 250 VAC (resistive); ½ HP @ 240 VAC ; ¼ HP @ 120 VAC
Trouble Contacts Rating:
(SPDT) 2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive)
AIR VELOCITY
100 to 4000 ft/min (0.5 to 20.32 m/sec)
AMBIENT TEMPERATURE
–4° to 158°F (–20° to 70°C); D4P120: –40° to 158°F (–40° to 70°C)
HUMIDITY
0% to 95% relative humidity non-condensing
DIMENSIONS
14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth
Shipping Weight (lbs.)
2.5
- Integrated Low-Flow Technology
- Flexible Enough to Fit Configurations from Square to Rectangular
- Plug-In Sensor Offers Superb False Alarm Immunity and the Latest Sensor Technology
- Patented Sampling Tube Installs from Front or Back of the Detector with no Tools Required
- Increased Wiring Space with a Newly Added 3/4 Inch Conduit Knockout
- One Easy-Access Test/Reset Button and Improved LED Status
- Patented Interconnect Feature for Multi-Fan Shutdown
- New High Contrast Terminal Designations
- Built-In Short Circuit Protection from Operator Wiring Errors
- Field Selectable Settings for Configuring the Detector
- Two DPDT Form-C Relay Contacts
- Backward Compatibility with Existing Innovair Products, Including Remote Accessories