Application
Hot Surface Ignition Control Module
Feature Supported
Hot Surface Ignition
Approvals and Standards
CSA Design Certified
Type of Fuel
Natural Gas, LPG
Ignition Type
Direct Hot Surface Ignition
Ignition Source
Line Voltage (120 VAC) Hot Surface Element (Norton Model 201 or 270)
Ignition Between Trail Time
(2) 96 sec- 3 trial mode only
Ignition Sequence
The number of trials for ignition and trial time is determined by the dip switch selection.
Ignition Trial Time
4 sec, 7 sec
Ignition Warm-Up Time
34 sec
Ignition Trials To Lockout
1 or 3
Interpurge
64 seconds
Pre-Purge
32 sec
Lockout Timing
4 sec, 7 sec
Flame Failure Response Time
1.5 sec
Flame Sense
Two Rod, Single Rod
Brands Supported
Universal
- Universal Hot Surface Ignition Module Replaces Multiple Field Installed
- Contains Easy-To-Use Cross Reference and Instructions
- The Accessories Required to Replace the Existing Hot Surface Ignition Module
- Provides One or Three Ignition Trials per Call for Heat
- Field Selectable Number of Ignition Trials and Trial Time Based on Unit Being Replaced